Design Requirements :
|
|
|
Model Rating
|
9000W/10000VA
|
|
Output Load Capacity
|
220 / 230 / 240
|
|
Internal Battery
|
Valve-regulated, non-spillable, lead acid cells.
|
|
Battery Reserve Time
|
Minimum 3 minutes with an ambient temperature of 25°C (77°F).
|
|
Battery Recharge
|
The UPS shall contain a battery charger designed to prolong battery life. Recharge time for UPS internal batteries shall be 3 hours maximum to 90% capacity after a complete discharge into full load.
|
|
Frequency
|
The UPS shall auto-sense mains frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency.
|
|
Mains Power Factor
|
>0.99 lagging at rated load.
|
|
Mains Output, UPS Inverters :
|
|
|
Voltage Configuration
|
50Hz, single-phase, 2-wire-plus-ground.
|
|
Voltage Regulation
|
L-N: ±3% steady state.
|
|
Frequency Regulation
|
±3.5Hz synchronized to mains.
|
|
Frequency Slew Rate
|
1.0Hz per second maximum
|
|
Load Power Factor Range
|
0.65 lagging to 1.0 (unity)
|
|
Voltage Distortion
|
Sinusoidal Waveform; ≤3% total harmonic distortion (THD) into a 100% linear load; ≤5% THD into a 100% non-linear load with a crest factor ratio of 3:1.
|
|
Voltage Transient Response
|
±7% on-line or Battery mode for 0-100-0 % loading of the UPS, ±4% on-line or Battery mode for 20-100-20 % loading of the UPS.
|
|
Transient Recovery Time
|
To nominal voltage within 166 milliseconds.
|
|
Efficiency
|
92% AC-AC
|
|
Accessories :
|
|
|
RMKIT 18 32
|
Rackmount Kit for GXT3
|