General specifications
|
|
Signal type
|
Analog input
|
|
Functional safety related parameters
|
|
Safety Integrity Level (SIL)
|
SIL 2
|
|
Supply
|
|
Connection
|
Power Rail or terminals 9+, 10-
|
|
Rated voltage
|
18 ... 30 V DC
|
|
Ripple
|
within the supply tolerance
|
|
Power dissipation
|
approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
|
|
Power consumption
|
2 W
|
|
Input(KCD2-STC-Ex1.2O倍加福安全柵)
|
|
Connection side
|
field side
|
|
Connection
|
terminals 1+, 2- (sink); 3+, 4- (source)
|
|
Input signal
|
0/4 ... 20 mA
|
|
Voltage drop
|
terminals 3, 4: ≤ 6.1 V at 20 mA
|
|
Short-circuit current
|
terminals 1+, 2-: 25 mA
|
|
Input resistance
|
terminals 1+, 2-: max. 500 Ω
(250 Ω load)
|
|
Available voltage
|
terminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA
|
|
Output(KCD2-STC-Ex1.2O倍加福安全柵)
|
|
Connection side
|
control side
|
|
Connection
|
source: terminals 5-, 6+; 7-, 8+
sink: terminals 5+, 6-, 7+, 8-
|
|
Load
|
channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
|
|
Output signal
|
0/4 ... 20 mA or 0/1 ... 5 V
|
|
Ripple
|
max. 50 ?A rms
|
|
Transfer characteristics
|
|
Deviation
|
Iout < 20 ?A (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V
|
|
|
Influence of ambient temperature
|
current output: 0.25 ?A/K
voltage output: 80 ?V/K
|
|
Frequency range
|
field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
|
|
Settling time
|
6 ms
|
|
Rise time/fall time
|
2 ms
|
|
Galvanic isolation
|
|
Output/power supply
|
functional insulation, rated insulation voltage 50 V AC
|
|
Output/Output
|
functional insulation, rated insulation voltage 50 V AC
|