TYPE
|
Transformer Turns Ratio Tester
|
|
PHYSICAL SPECIFICATIONS
|
Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
Weight: 8 lbs. (3.6 Kg)
|
|
INPUT POWER
|
120 or 240 Vac (Selectable), 50/60 Hz
|
|
MEASURING METHOD
|
ANSI/IEEE C57.12.90
|
|
RATIO MEASURING RANGE
|
0.8 - 15,000 (5 digit resolution)
|
|
TURNS-RATIO ACCURACY
|
40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%)
4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%)
|
|
TEST VOLTAGE
|
4 Vac @ 1.0A, 40 Vac @ 0.6A
|
|
PHASE ANGLE MEASUREMENT
|
0 - 360 degrees, Accuracy ±0.2 degree (±1 digit)
|
|
POLARITY READING
|
In-Phase or Out-of-Phase indication
|
|
EXCITATION CURRENT READING RANGE
|
0-2 Amperes, Accuracy: 2% of reading (±1 mA)
|
|
DISPLAY
|
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
|
|
COMPUTER INTERFACE
|
RS-232C
|
|
PC SOFTWARE
|
Windows XP/Vista/7 Transformer Analysis Software (included with purchase)
|
|
INTERNAL TEST RECORD STORAGE
|
128 records of 33 readings
|
|
EXTERNAL TEST RECORD STORAGE
|
Up to 999 test records on external USB Flash drive.
|
|
SAFETY
|
Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards
|
|
ENVIRONMENT
|
Operating: -10?C to 50?C (15?F to +122?F)
Storage: (-30?C to 70?C (-22?F to +158?F)
|
|
HUMIDITY (MAX)
|
90% RH @ 40? C (104? F) non-condensing
|
|
ALTITUDE (MAX)
|
2000m (6562 ft) to full safety specifications
|
|
CABLES
|
One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag
|
|
OPTIONS
|
Transportation Case (Can hold unit and cables)
|
|
WARRANTY
|
One year on parts and labor
|
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|