TYPE
|
Portable relay test set
|
|
INPUT POWER
|
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
|
|
PHYSICAL SPECIFICATIONS
|
17”W x 12.5”H x 12”D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg)
|
|
AMPERE METER INPUT RANGES
|
Internal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA,
External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC
|
|
VOLT METER INPUT RANGE
|
0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count
Measurement Method: True RMS for AC
|
|
AUXILIARY POWER SUPPLIES
|
24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A
|
|
POWER RESISTORS
|
5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W
|
|
SAFETY
|
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
|
|
ENVIRONMENT
|
Operating: -10?C to 50? C (15?F to +122? F); Storage: -30? C to 70? C (-22?F to +158? F)
|
|
OPTIONS
|
Transportation case
|
|
WARRANTY
|
One year on parts and labor
|
|
AC Current Output
|
|
Range
|
No-Load Voltage
|
Load Voltage
|
Load Current
|
Load/Unload Times
|
|
10 A
|
90 Vac
|
75 Vac
|
10 A
|
2 min / 15 min
|
|
40 A
|
25 Vac
|
20 Vac
|
40 A
|
1 min / 15 min
|
|
100 A
|
10 Vac
|
7.25 Vac
|
100 A
|
1 min / 15 min
|
|
100 A
|
10 Vac
|
3 Vac
|
250 A
|
1 sec / 5 min
|
|
|
AC Voltage Output
|
|
Range
|
No-Load Voltage
|
Load Voltage
|
Load Current
|
Load/Unload Times
|
|
250 Vac
|
260 Vac
|
240 Vac
|
3 A
|
10 min / 45 min
|
|
|
DC Voltage Output
|
|
Range
|
No-Load Voltage
|
Load Voltage
|
Load Current
|
Load/Unload Times
|
|
300 Vdc
|
300 Vdc
|
250 Vdc
|
2 A
|
10 min / 45 min
|
|
|
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable)
|
|
Range
|
Resolution
|
Accuracy
|
|
0 to 9.999 sec
|
1 ms
|
± (1 ms + 0.01%)
|
|
10.00 to 99.99 sec
|
10 ms
|
± (10 ms + 0.01%)
|
|
100.0 to 999.999 sec
|
100 ms
|
± (100 ms + 0.01%)
|
|
|
Timer Cycles Display
|
|
Range
|
Resolution
|
Accuracy
|
|
0 to 9.999 cycles
|
0.1 cycle
|
± (0.1 cycle + 0.01%)
|
|
1,000 to 49,999 cycles / 50 Hz
|
1 cycle
|
± (1 cycle + 0.01%)
|
|
|