TYPE
|
Portable current-transformer test set
|
|
PHYSICAL SPECIFICATIONS
|
16.8”W x 12.6”H x 12”D (42.7 cm x 32 cm x 26.9 cm); Weight: 55 lbs (25 Kg)
|
|
INPUT POWER
|
100 – 120 Vac or 200 - 240 Vac (factory pre-set), 50/60 Hz
|
|
MEASUREMENT METHOD
|
IEC 60044-1, IEC 61869, ANSI/IEEE C57.13.1, and ANSI/IEEE C57.12.90
|
|
OUTPUT TEST VOLTAGES
|
0 – 50 Vac @ 10A max; 0 – 200 Vac @ 10A max; 0 – 1200 Vac @ 1.5A max (5 min on, 10 min off)
|
|
VOLTAGE READING RANGE
|
0 – 1,250 Vac; Accuracy: ±1.0% of reading, ±0.5 volt
|
|
CURRENT READING RANGE
|
0 – 10A; Accuracy: ±1.0% of reading, ±0.02A
|
|
CURRENT-RATIO RANGE
|
0.8 – 99: ±0.5%, 100 – 999: ±1.0%, 1,000 – 5,000: ±2%
|
|
PHASE ANGLE MEASUREMENT
|
0 – 360 degrees; Accuracy: ±1.0 degree
|
|
DISPLAY
|
Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight and low-light levels
|
|
PRINTER
|
Built-in 4.5-inch wide thermal printer
|
|
COMPUTER INTERFACES
|
One RS-232C port, One USB port
|
|
PC SOFTWARE
|
Windows? XP/Vista-based software is included with purchase price
|
|
INTERNAL TEST RECORD STORAGE
|
Stores 128 test records. Each test record may contain up to 10 excitation and ratio data sets
|
|
INTERNAL TEST HEADER STORAGE
|
Stores 10 test header records
|
|
SAFETY
|
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
|
|
ENVIRONMENT
|
Operating: -10? to 50? C (15?F to +122? F); Storage: -30? C to 70? C (-22?F to +158? F)
|
|
CABLES
|
One 20-foot X cable set, One 35-foot H cable set, power cord, One cable carrying duffel bag
|
|
OPTIONS
|
Transportation case
|
|
WARRANTY
|
One year on parts and labor
|
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|