TYPE
|
Portable circuit-breaker analyzer
|
|
PHYSICAL SPECIFICATIONS
|
Dimensions: 21.5”W x 8”H x 14” D (53 cm x 20 cm x 35 cm)
Weight: 15 lbs (6.8 Kg)
|
|
INPUT POWER
|
100-240Vac, 3A, 50/60Hz
|
|
DRY-CONTACT INPUTS
|
3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time.
|
|
TIMING WINDOWS
|
1 second, 10 seconds, or 20 seconds
|
|
TIMING RESOLUTIONS
|
±50 micro-seconds @ 1 sec. duration,
±500 micro-seconds @ 10 sec. duration,
±1.0 milli-seconds @ 20 sec. duration
|
|
TIMING ACCURACY
|
0.05% of reading ±0.05 ms @ 1 second duration
|
|
DRY-CONTACT CHANNEL PROTECTION
|
All contact inputs are grounded until test. Input channels are also protected against static discharge.
|
|
DRY-CONTACT DETECTION RANGE
|
Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
|
|
INSERTION RESISTOR DETECTION RANGE
|
50 – 5,000 ohms
|
|
TRIGGER INPUT VOLTAGE
|
Open/Close trigger voltage: 24 V – 300V DC or peak AC
|
|
VOLTAGE SENSING INPUT RANGE
|
V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
|
|
BREAKER OPERATIONS
|
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
|
|
BREAKER INITIATE CAPACITY
|
30A, 250 Vac/dc max
|
|
INITIATE CURRENT READING RANGE
|
one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
|
|
DIGITAL TRAVEL TRANSDUCER INPUTS
|
3 channels, 200 ohm – 10K ohms
|
|
CONTACT TRAVEL POINT DIFFERENCE
|
measures “slow-close” contact-point distances; results can be printed
|
|
DISPLAY
|
back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
|
|
PRINTER
|
built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
|
|
INTERNAL TEST RECORD STORAGE
|
Store up to 200 test records and 100 test plans
|
|
EXTERNAL TEST RECORD STORAGE
|
USB Flash drive interface for external storage of test records and test plans
|
|
COMPUTER INTERFACES
|
One USB port, optional Bluetooth wireless interface
|
|
PC SOFTWARE
|
Windows? based Breaker Analysis software included with purchase price
|
|
CABLES
|
furnished with full set of test leads
|
|
OPTIONS
|
transportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
bluetooth interface
|
|
SAFETY
|
designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
|
|
ENVIRONMENT
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
|
HUMIDITY
|
90% RH @ 40°C (104°F) non-condensing
|
|
ALTITUDE
|
2,000 m (6,562 ft) to full safety specifi cations
|
|
WARRANTY
|
one year on parts and labor
|
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|