TYPE
|
Portable circuit-breaker analyzer
|
|
PHYSICAL SPECIFICATIONS
|
16”W x 7”H x 13” D (40.6 cm x 17.4 cm x 33 cm); Weight: 14 lbs. (6.4 Kg)
|
|
INPUT POWER
|
100 - 240 Vac, 50/60 Hz
|
|
DRY-CONTACT INPUTS
|
3 channels
|
|
TRIGGER INPUT VOLTAGE
|
open/close: 24 - 300 V, DC or peak AC
|
|
BREAKER OPERATIONS
|
Open, Close, Open-Close, Close-Open
|
|
TIMING RESOLUTION
|
±0.1 millisecond; accuracy: 0.05% of reading ±0.1 ms
|
|
DISPLAY
|
back-lit LCD screen (128 x 64 pixels); viewable in bright sunlight and low light conditions
|
|
KEYPAD
|
rugged, 44-key "QWERTY" membrane keypad
|
|
PRINTER
|
built-in 2.5-inch wide thermal printer
|
|
INTERNAL TEST RECORD STORAGE
|
stores up to 128 timing records
|
|
COMPUTER INTERFACE
|
one USB PC interface, one USB Flash drive interface
|
|
COMPUTER SOFTWARE
|
Windows? based Breaker Analysis software included with purchase price
|
|
SAFETY
|
designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
|
|
ENVIRONMENT
|
Operating: -10°C to +50°C (+15°F to +122°F)
Storage: -30°C to +70°C (-22°F to +158°F)
|
|
HUMIDITY
|
90% RH @ 40°C (104°F) non-condensing
|
|
ALTITUDE
|
2,000 m (6,562 ft) to full safety specifications
|
|
CABLES
|
furnished with full set of test leads (inluding 20-foot contact leads and 30-foot contact lead extensions)
|
|
OPTIONS
|
transportation case
|
|
WARRANTY
|
one year on parts and labor
|
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|